8.2.2 Regular maintenance
In order to make the inverter run normally for a long time, the electronic elements
mounted in inverter shall be maintained regularly. And the service life of electronic
elements is different with the service environment and service condition. The
maintenance period of inverter as shown in the table 8-2 is provided for referring.
Part name
Fan
Electrolytic capacitor
PCB
Fuse
Applicable condition for changing time of aforementioned inverter parts
(1) Environment temperature:Annual average is 30℃.
(2) Load factor: Less than 80%
(3) Running time: Less than 12 hours every da
Table 8-2 Changing time of inverter parts
Standard changing time
2~3 years
4~5 years
5~8 years
10 years
y
8-2