Host machine send(hexadecimal):01 06 20 00 00 1E 02 02
Slave machine response(hexadecimal):01 06 20 00 00 1E 02 02
Response information consistently show successful updated,command data stock
address is 2000H,command content combination refer to table3.
③ The given frequency of communication
For example:Given frequency 40.00HZ(0FA0H)to the address 01H slave machine
Host machine send(hexadecimal):01 06 20 01 0F A0 D6 42
Slave machine response(hexadecimal):01 06 20 01 0F A0 D6 42
Response information consistently show successful updated,the store address of
communication given frequency is 2001H.
(3)10H function code application
①Update two parameters continuously.
Parameter the first address refer to table1.
For example:Update the parameter P0.03 of address 01H slave machine to
1088H,and P0.04 is updated to 2(hexadecimal is 0002H)
Host machine send(hexadecimal):01 10 00 03 00 02 04 10 88 00 02 B6 91
Slave machine response(hexadecimal):01 10 00 03 00 02 B1 C8
The response massage is right which show update successfully. We can check that the
parameter P0.03,P0.04 have been modified from keyboard
②Send command,at the same time modify parameter.
When use 10H to send command, the first one data is command value(the
meaning refer to table3), the second one parameter is frequency parameter.