EasyDrive CV3100 Series Instruction Manual page 80

High performance general purpose inverter
Table of Contents

Advertisement

CV3100 series and MINI series high performance general purpose inverter instruction manual
Function of key REV/JOG on operating keypad can be set by this parameter, which
detailed setting as following:
0:This key is for REV running.
1:This key is for JOG running.
6.2 Motor and vector control parameter
P1.00
Motor rated voltage
Setting range
P1.01
Motor rated current
Setting range
P1.02
Motor rated rotation speed
Setting range
P1.03
Motor rated frequency
Setting range
P1.04
Motor no-loading current
Setting range
The above parameters are for electric parameters of motor droved. If the power of
motor is different from the inverter, the difference must keep within two-level grade,
and the value of P1.01 must be same as the rated current of motor in order to ensure
correct parameters checkout of motor when in motor auto tuning.
P1.05
Motor stator resistance
Setting range
P1.06
Motor rotor resistance
Setting range
Inductance of stator and
P1.07
rotor
Factory setting
200V—500V/100V—250V
Factory setting
0.1—600.0A
Factory setting
300—3000RPM
Factory setting
1.00—400.00Hz
Factory setting
0.1—500.0A
Factory setting
0.001—10.000Ω
Factory setting
0.001—10.000Ω
Factory setting
6-12
380V/220V
Determined by
inverter type
Determined by
inverter type
50.00Hz
0.1A
Determined by
inverter type
Determined by
inverter type
Determined by
inverter type