CV3100 series and MINI series high performance general purpose inverter instruction manual
6.7 Process PID control parameter
Analog feedback control system:
Pressure given quantity input through AI1 and 4-20mA signal feedback from pressure
sensor input through AI2 are connected with PID adjustor built-in to compose the
close loop control system, shown as Diagram 6-20:
contactor
supply
Forward/Stop
command
Diagram 6-20 Analog feedback control system
P6.00
PID actiong setting
Setting range
LED single digit:Function setting
0:Close
1:Open
LED tens digit:PID availability selection
0:Automatic availability
1:Manual availability by defining of multi-function terminal
LED Hundreds & thousands digit: Reserved
PID function as followings:
PID gives comparison to the system ration and feedback quantity which was detected
from the sensor to the object controlled, proceeding with operation of proportion,
integral and differential coefficient to their deviation in order to adjust the inverter
output frequency, applying for process control of physical quantity, such as flow,
pressure, temperature and so on, the system network shown as Diagram 6-21:
CV3100
R
U
S
V
T
W
FWD
COM
+10V
AI2
+24V
AI1
PLC
GND
00-11
6-42
External
transmission
P
M
4~20mA
Factory setting
00