EasyDrive CV3100 Series Instruction Manual page 91

High performance general purpose inverter
Table of Contents

Advertisement

CV3100 series and MINI series high performance general purpose inverter instruction manual
P2.36
Skip freq. 1
P2.38
Skip freq. 2
P2.40
Skip freq. 3
Setting range
P2.37
Skip freq. band 1
P2.39
Skip freq. band 2
P2.41
Skip freq. band 3
Setting range
Setting of above parameters is mainly used for avoiding mechanical resonance due to
the inverter running on the resonant frequency points. When the skip frequency is set,
the inverter will skip from the frequency points set them during running. No matter
accel and decel,speed,the frequency of inverter will pass these points. If the skip
frequency range is set to 0, the corresponding resonant frequency point has no
function of skip. The output frequency of inverter can perform skip operation at some
frequency points, shown as Diagram 6-10.
Skip freq 3
Skip freq 2
Skip freq 1
P2.42
Carrier frequency selection
Setting range
This parameter is used for setting carrier frequency of PWM wave by inverter output.
Carrier frequency will affect the noise of the motor running.In the mute occasion ,it is
0.0—Upper limit frequency
0.0—10.0Hz
Set freq after adjusting
Skip range 1
Diagram 6-10 Skip frequency action
1.0—12.0KHz
6-23
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting
Skip range 3
Skip range 2
Freq setting
Determinated by inverter type
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0.00Hz

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents