CV3100 series and MINI series high performance general purpose inverter instruction manual
P0.01
Frequency input channel selection
Setting range
0:Keypad potentiometer
Through the operation of potentiometer on the keypad to adjust running frequency
1:Digital setting 1
Operating frequency is set by parameter P0.03, which also can be changed by
operating the keypad ▲/▼ key or digital encoder in the course of running, the revised
frequency value will be stored into P0.03 when in power-down. If the frequency doses
not need storage, you can directly set parameters P0.02 in order to change frequency.
Note:
LCD keyboard does not provide analog potentiometer, but a digital encoder, which can
completely replace the ▲/▼ and SET button and their functions to achieve digital
frequency adjustment and function parameters amendment, as well as data storage,
making operation easy to the customer. So we particularly declare that when use of the
encoder, P0.01 should be set to "1" (digital setting 1) rather than "0", otherwise the
digital encoder for frequency setting will invalid. If the customers need to use analog
potentiometer to achieve a given frequency, please choose LED keypad or external
potentiometer.
2:Digital setting 2
Operating frequency by external terminals defined as UP/DOWN function.
UP-COM is closed, frequency rises; when DOWN-COM is closed, frequency decrease;
UP/DOWN with COM are closed or opened at the same time,frequency keeps at the
0
Panel potentiometer setting
Keypad setting by ▲/▼or digital encoder
1
2
UP/DOWN terminal digit setting
3
Communication setting
4
AI1 analog voltage signal setting(0~10V)
5
AI1 analog current signal setting(0~20mA)
6
Terminal pulse(0~20kHz)
7
Compounding setting
8
External terminal selection
6-2
Factory setting
0
When