CV3100 series and MINI series high performance general purpose inverter instruction manual
Specific meaning as follow:
Address:01H
Function:10H
Start address:000EH ----Register start address is 0x000E, indicates writing
content to 0x000E,0x000F
Data volume(word):0002H ----wrote content words volume(namely
register number)
Data volume(Byte):04------wrote content bytes volume。
The first one data :0064H wrote the first one content.
The second one data :0050H wrote the second one content
CRC CHK:Reference to the last page for methods to get RTU mode check
code (CRC Check).
Response the frame:01H+10H+00H+0EH+00H+02H+20H+0BH
Specific meaning as follow:
Address:01H
Function:10H
Starting address:000EH ----Register start address is 0x000E,Indicates
that start to write data from address 0x000E register
Data volume(word):0002H ----wrote content words volume(namely
register volume)。
CRC CHK:Reference to the last page for methods to get RTU mode check
code (CRC Check).
Special note,Response the frame only feedback 6 byte in the front of query the
frame , and its CRC CHK is the CRC CHK of these 6 bytes.
Communication application example:
● Parameter address definition of Communication protocol, show as table1
---- this device ID is 01H
---- write many registers function code
---- this device ID is 01H
---- write many registers function code
9-12