CV3100 series and MINI series high performance general purpose inverter instruction manual
or personnel because of unexpected startup of motor.
P2.17
Failure self-reset times
Setting range
Failure self-reset interval
P2.18
Setting range
During running, if the inverter is in fault, it will stop output and show out fault code.
After passing the time defined by P2.18, the inverter will self-reset from the failure
and go on running. The times of failure self-reset is specified by P2.17, if which was
set to 0, there is no self-reset function. Resetting the fault is only by hand pressing key
STOP/RESET.
The inverter do not allow to be self-reset to the failure of overheat of overload
P2.19
Jog running frequency
Setting range
Jog accel. time
P2.20
Jog decel. time
P2.21
Setting range
The above parameters specify the jog running parameters correlated, shown as the
following Diagram 6-9:
0-10
0.5-25.0s
0.00—50.00Hz
0.1—3600s
frequency
t1
Diagram 6-9 Jog running parameters
Factory setting
Factory setting
Factory setting
Determined by inverter type
Determined by inverter type
t3
t2
6-21
3.0s
10.00Hz
time
0