CV3100 series and MINI series high performance general purpose inverter instruction manual
SB1—Switch for stopping (constant closed)
K—Direction switch
K
0
1
P4.07
Open collector terminal DO1 output
P4.08
Open collector terminal DO2 output
P4.09
Programmable relay output
Setting range
0:Inverter running indication
When the inverter is running, it has effective signal output, or it will output ineffective
signal.
1:Frequency/speed arrival signal (FAR)
Please refer to P4.12 explanation for details.
2:Frequency/speed level detecting signal (FDT)
Please refer to P4.10 explanation for details.
3:Inverter zero speed running indication
Refers to inverter output frequency is 0.00HZ, but it is still be output indication signal
in the running stage at the moment.
4:Peripheral failure stop
During the inverter running, when digital (on-off quantity) input terminal receives
peripheral failure stop signal which results in failure stop, the inverter sends out
indication signal.
5:Output freq. arriving at the upper limit
Indication signal output of the inverter reaching the upper limit frequency.
6:Output freq. arriving at the lower limit
Indication signal output of the inverter reaching the lower limit frequency.
7:Programmable multi-step speed circular running finished
Indication signal output is from this terminal when one cycle of programmable
Running
Direction
FWD
REV
Diagram 6-14 Three-line control mode 2
0—15(refer to following explanation)
SB2
FWD
SB1
DI1
K
REV
COM
Factory setting
Factory setting
Factory setting
6-32
0
1
15