Terminal
Type
10V
GND
Power supply
COM
24V
PLC
Table 3-4 Control plate CN3 terminal function
3.6.3 Wiring of analog input/output terminal
(1) AI1 terminal accepting input of analog voltage signal, its wiring as follows:
(2) AI2 terminal accepting input of analog current and voltage signal, its wiring as
follows
Grounding of shielded
wire near terminal
Name
no.
+10V power
supply
+10V power
common terminal
+24V power
common terminal
+24VDC
Multi-function
input terminal
+
0~+10V
-
Diagram 3-10 AI1 terminal wiring
Terminal function
Provide +10V power
supply for external.
(Negative end: GND)
Analog signal and
reference ground of +10V
power supply
Input/output common
terminal of digital signal
Digital signal power
DI1-DI6 public terminal
CV3100
10V
AI1
GND
3-14
Spec.
Max output
current:20mA
Mutual inner isolation
shall be produced
between COM and GND.
Max
output
current:
50mA
Short circuit with 24V as
factory default