INVT Goodrive100-PV Series Operation Manual page 58

Solar pump inverter
Hide thumbs Also See for Goodrive100-PV Series:
Table of Contents

Advertisement

Goodrive100-PV Series Solar Pump Inverter
Fault
Fault type
code
EF
External fault
RS485
CE
communication fault
Current detection
ItE
fault
Motor autotuning
tE
fault
EEPROM operation
EEP
fault
PID feedback
PIDE
disconnection
Running time
END
reached
Possible cause
SI external fault input
terminals action.
The baud rate setting is
incorrect.
A fault occurs to the
communication wiring.
The communication
address is incorrect.
Communication
from strong interference.
The
control
connector
is
contact.
Hall device is damaged.
An exception occurs on
the magnifying circuit.
The motor capacity does
not match the inverter
capacity.
Motor parameters are
not set correctly.
The difference between
the parameters obtained
from autotuning and the
standard parameters is
great.
Autotuning timed out.
Error
in
reading
writing
parameters.
EEPROM is damaged.
PID
feedback
disconnected.
The
PID
source disappears.
The actual running time
of the inverter is longer
than
the
internal
-54-
Fault diagnosis and solution
Check the external device
input.
Set a proper baud rate.
Check the communication
interface wiring.
Set a proper
communication address.
Replace or change the
suffers
wiring to enhance the
anti-interference capability.
board
Check the connector and
in
poor
re-plug.
Replace the Hall device.
Change the main control
board.
Change the inverter mode.
Set the motor type and
nameplate parameters
correctly.
Empty the motor load.
Check the motor wiring and
parameter settings.
Check whether the upper
limit frequency is higher
than
frequency.
or
Press STOP/RST for reset.
control
Change the main control
board.
is
Check the PID feedback
signal wires.
feedback
Check the PID feedback
source.
Ask the supplier to adjust
the preset running time.
set
Solution
2/3
of
the
rated

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive100-PV Series and is the answer not in the manual?

Questions and answers

Hamse Ismael
March 9, 2025

I want to connect a low water level sensor to GD100-PV invt how it supposed to do

2 comments:
Mr. Anderson
March 9, 2025

The low water level sensor should be connected to the INVT Goodrive100-PV Series inverter at the designated terminal. Based on the standard wiring diagram:

1. Identify the low water level switch terminals.
2. Connect the common terminal of the sensor to the COM terminal on the inverter.
3. Connect the sensor output to the appropriate input terminal (e.g., S1 or S4) on the inverter.
4. Ensure wiring is secure and correctly configured according to the installation guidelines.

This setup allows the inverter to receive signals from the low water level sensor and respond accordingly.

This answer is automatically generated