Interfacing With The 4120 Network; Network Interface Card; Table 6-10. Network Interface Card  Jumper Positions; Table 6-11. Network Interface Card  Setting Card Number Via Sw2 - Simplex 4190 Graphical Installation And Instructions Manual

Graphical command center
Hide thumbs Also See for 4190 Graphical:
Table of Contents

Advertisement

Interfacing with the 4120 Network

Network Interface Card

Jumper
P1
P2
P3
P6
Address Range
*A Network Repeater card cannot serve as the network interface for point changes on the network.
This section explains how to install the 565-694 Network Interface Card (Wired)
or the 565-695 Network Interface Card (Modular).
You can install up to four Network Interface Cards into one PC to support a
multi-network configuration. Each Network Interface Card can support one
network containing up to 98 nodes. A GCC/NPU can support up to four
networks consisting of up to 392 nodes. Ensure that the jumpers are set to the
positions listed in Tables 6-10 and 6-11 for each network card used.
Table 6-10. Network Interface Card  Jumper Positions
565-694 & 695 Network Card
Position
–––––
BAUD RATE:
1-2
[default]
57.6 KBPS (Wired)
2-3
9600 BPS (Modem)
PROTOCOL:
1-2
[default]
9-Bit (Wired)
2-3
8-Bit (Modem)
–––––
Table 6-11. Network Interface Card  Setting Card Number Via SW2
SW2-4
SW2-3
200 - 207
OFF
2B0-2B7
OFF
2B8-2BF
OFF
2C0-2C7
OFF
2C8-2CF
OFF
2D0-2D7
OFF
300-307
OFF
308-30F
OFF
firealarmresources.com
565-202 Network Card Function
Function
Position
1-2
–––––
1-2
[default]
2-3
1-2
1-2
–––––
2-3
SW2-2
SW2-1
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
6-9
Function
Enable Wired, Fiber
communication
BAUD RATE:
57.6 KBPS (Wired)
9600 BPS (Modem)
Enable Wired, Fiber
communication
PROTOCOL:
9-Bit (Wired)
8-Bit (Modem)
Device
Not Used
Network Card #1 (Default)
Network Card Repeater* #2
Network Card Repeater* #3
Network Card Repeater* #4
TBD
TBD
TBD
Continued on next page