M800VW/M80VW Series Connection and Setup Manual
44 Appendix 4: EMC Installation Guidelines

44.6 EMC Countermeasure Parts

44.6 EMC Countermeasure Parts

44.6.1 Shield Clamp Fitting

The effect can be improved by directly connecting the cable's shield sheath to the grounding plate as shown below.
Install the grounding plate near the outlet (within 10cm) of each panel, and press against the grounding plate with the clamp
fitting.
If the cables are thin, several can be bundled and clamped together.
To provide sufficient frame ground, install the grounding plate directly on the cabinet or connect with a grounding wire.
A
Ground Plate #D
100
Ground Plate #E
70
Clamp fitting A
Clamp fitting B
Outline drawing
Earthing plate
2-
5
hole
Installation hole
6
M4 screw
35
IB-1501612-C
B
C
86
30
Clamp fitting A × 2
56
-
Clamp fitting B × 1
L1 (maximum dimension when it is open)
25
12
Clamp fitting
(Fitting A, B)
View of clamp section
17.5
22
(Note 1) Screw hole for wiring to earthing plate in cabinet.
(Note 2) The earthing plate thickness is 1.6mm.
Enclosed fittings
L2 (reference dimension)
Peel the cable sheath at the clamp section.
Cable
Earthing plate
Cable
Shield sheath
Clamp fitting
L1
L2
[Unit: mm]
644
(77)
(54)