44 Appendix 4: EMC Installation Guidelines
44.5 Measures for Wiring in Panel

44.5.2 Shield Treatment of Cables

Use shielded cables for wiring outside the panel.
Use shield clamps within 10 cm of the lead-out port from the panel. (Refer to "44.6.1 Shield Clamp Fitting".)
 DC power supply cable [J070/J071 cable]
Operation panel
Personal
computer unit
Operation panel
I/O unit
 Use a shield clamp within 10 cm from the panel's inlet/outlet.
 When using a ferrite core, install it on both ends of the connected units.
 Always install a ferrite core (Refer to "44.6.2 Ferrite Core") on the general-purpose stabilized power supply.
The ferrite core may not be required depending on the selected power supply.
 Remote I/O cable [J210 cable]
Control panel
Control unit
J210 cable
 Use a shield clamp within 10 cm from the panel's inlet/outlet.
 When using a ferrite core, install it on both ends of the connected units.
IB-1501612-C
Shield clamp
General-purpose
stabilized power supply
J070/J071 cable
General-purpose
stabilized power supply
J070/J071 cable
Ferrite core
Shield clamp
Control panel
Remote I/O unit
Ferrite core
Control panel