Using The Sounder/Relay Base Wizard; Activating Base On Alarm - Simplex 4007ES Programmer's Manual

Fire alarm systems
Hide thumbs Also See for 4007ES:
Table of Contents

Advertisement

Custom Control, Continued
Using the
Using the Sounder/Relay Base Wizard you can change the default operation of single station
smoke detectors. Note that the default operation—sounder activates when the alarm threshold
Sounder/Relay
is passed and deactivates when the smoke level drops back below the threshold—is
Base Wizard
programmed using the TPHOTO device type. To use the wizard to change the default
operation, you must assign a device type of SPHOTO or RPHOTO to the device.
1. Start the Sounder/Relay Base Wizard by clicking on the Sounder/Relay Base Operation Wiz-
ard tab, which is located along the bottom left part of the Custom Control window.
2. Right click in the blank area above the tabs. When the list of options appears, select Create
Point Group. A figure similar to appears.
.
3. Enter a Name for the group in the Point Group field and enter any comments in the
Comments box. Click Next to continue. Refer to the appropriate section below for specific
information.
Activating Base
Activate base on Alarm configures the single station detectors to activate when the alarm
threshold is reached and to turn off on either reset or silence.
on Alarm
1. To select this option, select the radio button labeled "Alarm—Activate Base on Alarm."
2. If necessary, you can select a different Custom Control user program. To do this, click on the
control to the right of Program # and select the appropriate program number. Click Next to
continue.
.
Figure 9-24. Creating Point Group
Figure 9-25. Sounder/Relay Base Information
9-15
4007ES Panel Programmer Manual (579-1167)
Continued on next page