Iso Options; Repeater Options - Simplex 4007ES Programmer's Manual

Fire alarm systems
Hide thumbs Also See for 4007ES:
Table of Contents

Advertisement

Point Editing for TrueAlert Device, Continued

ISO Options

Use this device type to edit TrueAlert Isolators. The following editing options are available for
this device:
Custom Label

Repeater Options

Use this device type to edit Repeaters.
The 4009 IDNAC Repeater is a TrueAlert ES Addressable device that extends the maximum
wiring distance supported by the IDNAC Signaling Line Circuit (SLC). Consult the 4009
IDNAC Repeater manual 579-1019 for more information. The following editing options are
available for this device:
Custom Label
Current Draw
(Amps)
Depleted Battery
Cutout
Repeater
Operation
Table 7-10.TrueAlert Isolator Editing Options
Option
This field can be used to describe the appliance's function, location, or other
descriptive information.
Table 7-11. Repeater Editing Options
Option
This field can be used to describe the appliance's function, location, or other
descriptive information.
This information is not available.
When this option is selected the Repeater shuts itself off after detecting a depleted
battery condition when no AC power is present. This option is de-selected by default.
Select the option that corresponds to the Repeater's wiring style.
• For local Class B Wiring select "Class B Spur"
• For local Class A Loop Wiring select "Class A Spur"
• For extended Class A Loop Wiring select "Class A Loop"
4007ES Panel Programmer Manual (579-1167)
Description
Description
7-15

Hide quick links: