Releasing Specific Controls and Indications, Continued
Discharge LED
Discharge LED Programming (RED LED) is required for every Hazard Area.
Programming
The Discharge LED activates when the suppression release device is in the released state
(RED LED)
(solenoid is activated). The LED clears upon system reset or when the solenoid is deactivated.
Below is an example program.
1. Click the Custom Control tab.
2. Click the Suppression Release Wizard subtab.
3. Right-click the title (next to the wizard graphic) and select Properties to open the Hazard
Area.
4. Select the Points tab and write down the List assigned to Suppression Dump Points.
5. Choose an available RED LED on the LED Module located under the Hardware tab. Set its
mode as "ON" and set the reference address to the list that was assigned.
4007ES Panel Programmer Manual (579-1167)
A-9