Custom Control, Continued
Suppression
Suppression release device and point types are shown in the table below. Assign the applicable
device and point types to the suppression points before programming hazard area information.
Release Device
and Point Types
Refer to section Programming Points inside the Online Help of the 4007ES Panel Programmer
for information on programming the points.
Point Type
Description
RELSIG
Releasing
audible circuit
RELISIG
NYC
investigation
bell/strobe
circuit
RELVIS
Release visual
circuit
RELWVIS
Releasing
warning visual
signal
SSABRT
Shorted
Suppression
Agent Abort
Zone
SSDUMP
Shorted
Suppression
Agent Manual
Dump
SUPRELS
Suppression
Release Output
SUPRELS
Suppression
(Graphic24)
(Agent
Discharge)
Release Output
Table 9-2. Valid Device and Point Types
Valid Device Types
SIGA, SIGB, CHAN2A, CHAN2B, CHAN4A,
CHAN4B, PCHAN4A, PCHAN4B, SIGIAM,
NULLSIG, PS_SIGA, PS_SIGB,
MFIO_SIGA, MFIO_SIGB, MSOUND,
MSIGA, MSIGB, VNAC
SIGA, SIGB, CHAN2A, CHAN2B, CHAN4A,
CHAN4B, PCHAN4A, PCHAN4B, SBZAM,
SAZAM, NULLSIG, PS_SIGA, PS_SIGB,
MFIO_SIGA, MFIO_SIGB, MSOUND,
MSIGA, MSIGB, VNAC
SIGA, SIGB, CHAN2A, CHAN2B, CHAN4A,
CHAN4B, PCHAN4A, PCHAN4B, SBZAM,
SAZAM, SIGIAM, NULLSIG, PS_SIGA,
PS_SIGB, MFIO_SIGA, MFIO_SIGB,
MSOUND, MSIGA, MSIGB, VNAC
SIGA, SIGB, CHAN2A, CHAN2B, CHAN4A,
CHAN4B, PCHAN4A, PCHAN4B, SBZAM,
SAZAM, SIGIAM, NULLSIG, PS_SIGA,
PS_SIGB, MFIO_SIGA, MFIO_SIGB,
MSOUND, MSIGA, MSIGB, VNAC
MONA, MONB, SMONA, SMONB,
SCAN50, 4002MA, 4002MB, IAM, SECIAM,
MAZAM, MBZAM
MONA, MONB, SMONA, SMONB,
SCAN50, 4002MA, 4002MB, IAM, SECIAM,
MAZAM, MBZAM, ADRPUL, CANPUL
RELEASE, SIGA, SIGB, CHAN2A,
CHAN2B, CHAN4A, CHAN4B, PCHAN4A,
PCHAN4B, SBZAM, SIGIAM, SAZAM,
NULLSIG, PS_SIGA, PS_SIGB,
MFIO_SIGA, MFIO_SIGB
OUTPUT
9-20
4007ES Panel Programmer Manual (579-1167)
AutoGenerates to Following Lists:
L0
- Coding Group 0
L1
- Coding Group 1
L50 - Walk Test Group 0 - signals/relays
L139- Local Mode Operation Points
L0
- Coding Group 0
L1
- Coding Group 1
L48 - TrueAlert Zone OFF on SILENCE
L50 - Walk Test Group 0 - signals/relays
L139- Local Mode Operation Points
L0
- Coding Group 0
L13 - Fire Alarm Visuals OFF on RESET
L49 - TrueAlert Zone OFF on RESET
L50 - Walk Test Group 0 - signals/relays
L139- Local Mode Operation Points
L0
- Coding Group 0
L13 - Fire Alarm Visuals OFF on RESET
L49 - TrueAlert Zone OFF on RESET
L50 - Walk Test Group 0 - signals/relays
L139- Local Mode Operation Points
L18 - General Fire Alarm Monitor Zones
L30 - Alarm Verification Group 0
L61 - Coding Group 1 - Monitor Zones
L139- Local Mode Operation Points
Continued on next page