Simplex 4007ES Programmer's Manual page 101

Fire alarm systems
Hide thumbs Also See for 4007ES:
Table of Contents

Advertisement

Custom Control, Continued
Common Ground
Select and utilize the LED Yellow point type for custom control ground fault LED trouble
indications:
Fault LED Control
Program the Color User Interface, Point Editing Tab as follows:
Add the following custom control equation to the 4007ES IDNAC Addressable Panel:
[INPUTS]
[END INPUTS]
[OUTPUTS]
[END OUTPUTS]
Add the following custom control equation to the 4007ES Hybrid Panel:
[INPUTS]
[END INPUTS]
[OUTPUTS]
[END OUTPUTS]
HW Ref.
Switch Mode
Ref. Address
3-1-1
SMPL
3-2-1
3-1-2
SMPL
3-2-2
3-1-3
SMPL
3-2-3
STATUS ON
1-0-9 | CARDSTAT | CSP | POSTIVE EARTH
OR STATUS ON
1-0-10 | CARDSTAT | CSP | NEGATIVE EARTH
OR STATUS ON
1-0-27 | CARDSTAT | CSP | POSITIVE EARTH ON RUI
OR STATUS ON
1-0-28 | CARDSTAT | CSP | NEGATIVE EARTH ON RUI
OR STATUS ON
2-0-8 | CARDSTAT | CSP | IDNET+ EARTH TROUBLE
TRACK ON PRI=9,9
P535 | DIGITAL | UTILITY | COMMON GROUND FAULT LED
STATUS ON
1-0-3 | CARDSTAT | CSP | POSITIVE EARTH GROUND
OR STATUS ON
1-0-4 | CARDSTAT | CSP | NEGATIVE EARTH GROUND
OR STATUS ON
2-0-8 | CARDSTAT | CSP | IDNET+ EARTH TROUBLE
TRACK ON PRI=9,9
P535 | DIGITAL | UTILITY | COMMON GROUND FAULT LED
9-17
4007ES Panel Programmer Manual (579-1167)
Ref. Label
HW Ref.
LED Mode
ON
P535
Ground Fault
SMPL