Advertisement

5 Default programming assignments

5.1

IDC, NAC, and relay default function types

For information on the default function types of IDCs, NACs and relays, see Table 2.
The function type of IDCs and NACs is a programmable attribute that you can manually change.
Circuit
IDC1-4
NAC1
AUX1 (Relay 1)
AUX2 (Relay 2)
AUX3 (Relay 3)
For an explanation of relay functions, see the follow points:
• RRELAY: Relay activates on general alarm; it remains on-until-reset.
• Common Trouble: Relay activates when a Trouble condition occurs; remains on-until-cleared.
• Common Supervisory: Relay activates when a Supervisory condition occurs; remains on-until-cleared.
5.2

NAC, relay, and signal circuit output mode assignments

See Table 3 for default, output, method (steady, temporal, for example) assignments for the NAC and Relay circuits.
The operating of NAC is a programmable attribute that you can manually change.
Circuit
NAC1
Relay 1 to 3
SIGNAL Modules
5.3

DACT defaults

Default NAC is enabled, the rest setting can be configured through the PC tool.
Function type
FIRE
WSO
SUPV
VSMOKE
Note: Any other trouble not specifically mentioned would have a code of 330. For example, a trouble on an output device reports an event
code of 330.
page 10
Table 2: Default function types of IDC, NAC, and relay
Default function type
Fire
QALERT
Common Trouble
Common Alarm, On Until Reset (RRELAY)
Common Supervisory
Table 3: Default operating modes of NAC, relay and signal circuit outputs
Operating mode
Temporal Code: A three pulse coding pattern consisting of three 1/2 second pulses, each separated
by 1/2 second silence. Each group of three pulses is separated by 1.5 seconds of silence
Steady on
Steady on
Table 4: Default CID event codes
Fire
110
110
-
111
2004 Foundation Series Fire Alarm Control Unit Operation Guide
Supervisory
-
200
200
-
Trouble
330
330
330
330
579-1403 Rev A