Simplex 4007ES Programmer's Manual page 74

Fire alarm systems
Hide thumbs Also See for 4007ES:
Table of Contents

Advertisement

Point Editing for TrueAlert Device, Continued
TrueAlert A/V
Use this device type to edit TrueAlert Strobe Audible/Visual (A/V) appliances. The following
Appliances Point
editing options are available for this appliance:
Editing
Custom Label
Style
Operation
Candela
Coding Type
Volume
Note: The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.
Table 7-15. TrueAlert AV Point Editing Options
Option
This field can be used to describe the appliance's function, location, or other
descriptive information.
Select the Style that corresponds to the appliance or device you are programming.
Indoor.
Available candela
options:
The strobe and horn appliances is automatically associated respectively with the "ALL
VISUAL" and "ALL AUDIBLE" VNAC by default.
Select the candela output of the appliance.
Select the Coding Type to set the cadence of the audible signal.
System Default
Temporal
March 60
March 120
On Steady
Set the appliance volume:
High
Low
4007ES Panel Programmer Manual (579-1167)
Description
System Default. Sets the candela value to the one selected in
the System Option tab.
15 candela
30 candela
75 candela
110 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
This sets the coding to the value determined in the System
Option tab.
A three-pulse coding pattern consisting of three ½ second
pulses, each separated by a ½ second silence. Each three
pulse group is separated by 1 ½ seconds of silence. Pattern
repeats until alarm silence.
A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats
until alarm silence.
A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off. Pattern repeats
until alarm silence.
On steadily.
To use this option the appliance's configuration control must be
set to Panel.
To use this option the appliance's configuration control must be
set to Panel.