Custom Control, Continued
Suppression
Initial data window
Release Use
Cases
Timer Configurations
Hazard Area Lists window
Use Case #1: 10 Second Delay Abort
Specific Configuration
Abort Logic Window
Table 9-3 describes actions and their corresponding responses.
Action
First detector is triggered.
Manual device or second detector is triggered.
Abort switch is pressed and maintained for
approximately 60 seconds after the RELSIG is in
high cadence.
Release the Abort Switch
• Program#: 3.
Note: It is always 3 for a 4007ES FACP.
• Check Enhanced Power Supply because we have an IDNAC channel.
• Check Cross Zone (Dual Detector).
• Set First Stage Audible Notification to Temporal.
Note: The other options are Slow March Time (March20) and Fast March Time (March120). Fast
March Time should not be used because the Second Stage Audible Notification is fixed at
Fast March Time.
• Set Manual Release at 30 seconds and check the box.
• Set Detector Release Delay at 60 seconds and check box.
• Press Manual Release Points and select the manual release point at M1-11-0.
• Press Automatic Release Points and select Automatic Release Points at M1-18-0
and M1-19-0.
• Press Abort Switches and select Abort Point at address M1-35.
• Press Release Warning Points and select SIG914.
• Press Suppression Dump Points and select SIG3 and M1-36-0.
• Press Release Notification Audible NACs and select SIG913.
• Set System Release after GREATER of Remaining Time Delay or 10 seconds.
Table 9-3. 10 Second Delay Abort, Actions and Responses
9-23
4007ES Panel Programmer Manual (579-1167)
Response
RELSIG turns on at low cadence (Temporal).
RELWVIS turns on.
RELSIG turns on at high cadence (March120).
RELWVIS stays on.
While the abort switch is pressed the RELSIG stays
in high cadence and RELWVIS stays on.
RELSIG stays on in high cadence. RELWVIS stays
on for 10 seconds or for the remainder of the
automatic release timer, whichever is greater. When
the timer expires RELSIG and SUPRELS turn on
steady and RELWVIS remains on.
Continued on next page