Editing Standard Component Properties, Continued
Editing the IDNAC
To edit the Data Entry tab (Figure 6-7):
Power Supply
1. Configure the Depleted Battery Cutout
option. If selected, the power supply card
shuts itself off after detecting a depleted
battery condition when no AC power is
present. If this option is selected, a jumper
must be installed on the power supply (on
S527), for Canadian operation. It is
unselected by default.
2. Select the optional cards that are
connected to the power supply card. The
choices are:
3. Click in the 25V Regulator box if a 25V regulator card, 4007-9802, is used with the FACP.
4. Click OK to confirm the selection.
To Edit the Aux Relay tab
(Figure 6-9):
1. Select a point type from the drop-
down menu.
2. Edit the Aux Relay point type
custom labels. This label should
make the point easily identifiable.
3. Click on Apply > OK to confirm
the edits.
• None
• City Connect
• Relay
Figure 6-8. IDNAC - AuxNAC Tab
6-6
4007ES Panel Programmer Manual (579-1167)
Figure 6-7. IDNAC - Data Entry Tab
To edit the AuxNAC tab
(Figure 6-8):
1. Select a point type
from the drop-down
menu.
2. Edit the AuxNAC point
type custom label. This
label should make the
point easily identifiable.
3. Click on Apply > OK
to confirm the edits.
Figure 6-9. IDNAC - Aux Relay Tab