Simplex 4007ES Programmer's Manual page 28

Fire alarm systems
Hide thumbs Also See for 4007ES:
Table of Contents

Advertisement

Panel Information and Configuration, Continued
System Options
General Description: These options stop a recurring trouble event from continuously dialing
the central station or from generating SafeLINC email events if the programmed criteria are
met (number of occurrences of that point in the trouble log within the specified elapsed time
frame).
Occurrences
Elapsed Time
General Description: This option allows System Options to be selected for TrueAlert ES
appliances that can be configured identically or independently through the ES Programmer
software.
To use the System Options to configure TrueAlert ES appliances:
• The appliance's jumpers and configuration switches must be set to the correct setting. For
example, if a specific candela value is selected in the system options, the device should be
set to FACP. On the other hand, if system option is set to "Hardware", the candela flag at the
device should be set to any other position than FACP.
• The appliance's candela and coding type in the power supply's Point Editing tab in the
programmer must be set to "System Default".
When a specific candela value is selected, that value applies to all compatible appliances that
have their configuration switches set to FACP*.
When Hardware Specified is selected, it is the appliance's locally configured candela value that
is used.
Candela
*Note: When a specific candela value is selected, a warning window appears to notify the user that in the
Table 4-4. Recurring Trouble Filter System Options
Option
Number of times the point is found in the Trouble log (0=no filtering; default for
pre-existing jobs upgraded to 12.06). Value is selectable from 0 and 2 to 10.
By default, it is set to 3.
Number of minutes in which the Troubles must be found. Value is selectable
from 1 to 1440 minutes. By default, it is set to 60.
Table 4-5. Addressable Appliances Preferred Default System Options
Option
• 15 cd
• 20 cd
• 30 cd
event that an appliance cannot be set to the selected Preferred Default System Option, a
compatible default value is assigned to the device by the programmer.
For example: If the System Option is set to 20 cd and there is a UL Weatherproof device (that has
no 20 cd setting), the Programmer assigns a value of WP75 cd to the UL weatherproof device.
4007ES Panel Programmer Manual (579-1167)
Description
System Options
• 75 cd
• 185 cd
• 110 cd
• Weather Proof 75 cd
• 135 cd
• Weather Proof 185 cd
4-6
• Hardware
Specified
Continued on next page

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4007es hybrid

Table of Contents