Custom Control, Continued
Using the
Selective Signaling is typically used to limit the activation of NACs to the area or floor on
which an activated initiating devices is located. In the following example, an activated
Selective
initiating device on Floor 2 triggers only the NACs located on Floor 2.
Signaling Wizard
Selecting
Start the Selective Signaling Wizard by clicking on the Selective Signaling Wizard tab, which
is located along the bottom left part of the Custom Control window.
Selective
Signaling Wizard
Right click in the blank area above the tabs. When the list of options appears, select Create
Tab
Group. (See Figure 9-19.)
The dialog shown in appears, prompting you for the name of the area/group. Enter a name for
the group in the dialog and click Next.
.
Figure 9-18. Selective Signaling
Figure 9-19. Create Selective Signaling Group
Figure 9-20. Naming Group
9-12
4007ES Panel Programmer Manual (579-1167)