Simplex 4007ES Manual

Simplex 4007ES Manual

Fire control panels
Hide thumbs Also See for 4007ES:

Advertisement

UL, ULC, CSFM Listed;
FM, NYC Fire Dept Approved*
Features
Satisfies a variety of new and retrofit applications
4.3" (109 mm) diagonal color touchscreen display:
 Provides detailed system status and point information
 Supports dual language selection, including unicode
character languages
 A custom background display appears when operation is
normal (see page 6 for details)
Eight Point Zone/Relay Module:
 Each point is selectable as an IDC input or Relay output,
Class A IDCs require 2 points (one out and one return);
one module is standard, up to 3 additional modules can
be field installed for a total of 4 eight point zone/relay
modules per system
 Each point on the IDC/Relay Module can be configured
as a control relay rated 2 A @ 30 VDC (resistive) as
either normally open or normally closed
 Can be powered directly from the power supply or
through the optional 25 VDC Regulator Module
 IDC end-of-line resistor value can be selected from a
wide range of resistance values for retrofit convenience
Electrically isolated IDNet+ addressable initiating
device SLC:
 Provides built-in short circuit isolation for monitoring
and control of TrueAlarm analog sensors and IDNet
communications monitoring and control devices; for use
with either shielded or unshielded, twisted or untwisted
single pair wiring; outputs are Class A or Class B
 Standard panel SLC provides up to 100 addressable
points; optional additional loop expansion modules
provide an additional isolated loop with short circuit
isolation for the IDNet+ channel; each loop expansion
module also provides an additional 75 addressable points
Power Supply Features:
 Four Notification Appliance Circuits (NACs) selectable
as Class A or Class B with 6 A total available current
 NAC end-of-line resistor value can be selected from a
wide range of resistance values for retrofit convenience
 Additional notification power capacity is available using
the 4009 IDNet NAC Extender
 Battery backup charging of up to 33 Ah; up to 18 Ah for
cabinet mounted batteries and up to 33 Ah batteries for
mounting in close-nippled remote battery cabinet
General Mechanical:
 Red or platinum cabinet; rated NEMA 1 and IP30
4007ES Listings reference:
 UL 864 - Control Units, System (UOJZ); Control Unit
Accessories, System, Fire Alarm (UOXX); Control
Units, Releasing Device Service (SYZV)
 UL 2017 - Emergency Alarm System Control Units (CO
detection), (FSZI)
 ULC-S559 - Central Station Fire Alarm System Units
(DAYRC)
 ULC-S527 - Control Units, System, Fire Alarm
(UOJZC); Control Unit Accessories, System, Fire Alarm
(UOXXC); Control Units, Releasing Device Service
(SYZVC)
4007ES Fire Control Panels
4007ES Hybrid, Fire Detection and Control Panel with
Addressable and/or Conventional Initiation
4007ES Hybrid Panel Front View
Software Feature Summary:
 Current and previous panel configuration maintained in
on-board memory
 An internal Ethernet service port is available for service
computer connections to perform configuration updates,
downloads and uploads; report downloads, and system
software
 Internal USB interface allows a memory stick to store job
revisions, update revised jobs and panel software, and save
detailed system reports from the panel
Optional modules and connections include:
 Fire Alarm Network Interface for Peer-to-Peer fire alarm
network communications, supports either Class B or Class
X operation
 Point or Event DACT assembly for IP Communicators
 Up to two additional IDNet+ addressable device output loop
connections with short circuit fault protection and with 75
additional point capacity each
 Front mounted 48 LED annunciator with custom label
inserts; LEDs are programmable for up to 24 IDC zones of
alarm and trouble annunciation or other custom
annunciation requirements
 Remote LED annunciator support via RUI communications
port for use with UTP wiring
 Dual RS-232 ports (for printer, PC annunciator or third party
interface)
 TrueInsight Remote Gateway
 Alarm relays and auxiliary relays
 City connections, with or without disconnect switch
 4003EC Voice Control Panels
 4009 IDNet NAC Extenders to extend NAC capability for
power and distance
 Battery brackets for seismic area protection (see page 2)
* This product has been approved by the California State Fire Marshal (CSFM)
pursuant to Section 13144.1 of the California Health and Safety Code. See
CSFM Listing 7165-0026:0378 for allowable values and/or conditions
concerning material presented in this document. NYC Fire Dept COA #6191A.
Additional listings may be applicable; contact your
local Simplex product supplier for the latest status. Listings and approvals
under Simplex Time Recorder Co. are the property of Tyco Fire Protection
Products.
S4007-0001-10 1/2017

Advertisement

Table of Contents
loading

Summary of Contents for Simplex 4007ES

  • Page 1 Additional listings may be applicable; contact your (UOXXC); Control Units, Releasing Device Service local Simplex product supplier for the latest status. Listings and approvals (SYZVC) under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. S4007-0001-10 1/2017...
  • Page 2: Operator Interface

    Introduction Operator Interface Features (Continued) 4007ES Series Fire Detection and Control Panels  Alarm and Trouble History Logs (up to 1000 entries for provide extensive installation, operator, and service features each, 2000 total events) are available for viewing from the...
  • Page 3: Operator Screen Reference

    Operator Screen Reference Main Menu Screen provides easy navigation to the function System Alarm Screen identifies active alarms with custom required. Buttons A, B, and C have programmable functions. labels displayed, arrows allow navigation through the list May 27, 2015 Main Menu 12:24 PM System Trouble Screen identifies active troubles with...
  • Page 4 IDNet+ Addressable Device Control Overview. The 4007ES Hybrid provides an IDNet+ TrueAlarm heat sensors can be selected for fixed addressable initiating device Signaling Line Circuit (SLC) that temperature detection, with or without rate-of-rise detection. supervises wiring connections and the individual device Utility temperature sensing is also available, typically to communications status on the SLC.
  • Page 5: Power Supply Output And Zone/Relay Module Details

    Description Supv. Alarm 4007ES Hybrid with 4 conventional 3 A NACs and a 6 A output power supply/battery 4007-9101(BA) charger; includes IDNet+ communications for 100 addressable points and 1, 4007-9801 Zone/Relay module; Note: Add optional module and other currents separately for battery...
  • Page 6: General Specifications

    Auxiliary Power Tap 2 A maximum, 24 VDC nominal (19.5 to 31.1 VDC) Special Application Non-Addressable Simplex horns, strobes, and combination horn/strobes and speaker/strobes Appliances (contact your Simplex product representative for compatible appliances) Power for other UL listed appliances; use associated external synchronization...
  • Page 7: 4007Es Mounting And Module Location Reference

    579-1109 Zone/Relay Module Installation Manual 579-1103 2-Wire Detector Compatibility Chart 579-832 Detailed Operator’s Manual 579-1165 4007ES Mounting and Module Location Reference 20-7/8" (530 mm) 16" (406 mm) 20-3/16" (512 mm) Side View Reference Finished wall surface (including semi-flush Trim Kit if used) Exposed box for semi-flush mounting 1-3/4"...
  • Page 8: 4007Es Hybrid Additional Reference

    S4190-0011 for 4007ES TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA). Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4007-0001-10 1/2017 www.simplex-fire.com...