Point Editing for TrueAlert Device, Continued
TrueAlert Horn
Use this device type to edit TrueAlert Horn appliances. The following editing options are
Appliance Point
available for this appliance:
Editing
Custom Label
Style
Coding Type
Volume
Note: The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.
Table 7-14. TrueAlert Horn Point Editing Options
Option
This field can be used to describe the appliance's function, location, or other
descriptive information.
Select the Indoor Style
Select the Coding Type to set the cadence of the audible signal.
System
This sets the coding to the value determined in the System Option tab.
Default
Temporal
A three-pulse coding pattern consisting of three ½ second pulses,
each separated by a ½ second silence. Each three pulse group is
separated by 1 ½ seconds of silence. Pattern repeats until alarm
silence.
March 60
A coded signal that uses 60 beats per minute. Each beat consists of ½
second pulse on, ½ second off. Pattern repeats until alarm silence.
March 120
A coded signal that uses 120 beats per minute. Each beat consists of
¼ second pulse on, ¼ second off. Pattern repeats until alarm silence.
On Steady
On steadily.
Set the appliance volume:
High
To use this option the appliance's configuration control must be set to
Panel.
Low
To use this option the appliance's configuration control must be set to
Panel.
7-17
4007ES Panel Programmer Manual (579-1167)