Point Editing for TrueAlert Device, Continued
TrueAlert ES AV-L
Use this device type to edit TrueAlert ES Audible/Visual LED Strobe (AV-L) appliances. The
Appliance Point
following editing options are available for this appliance:
Editing
Custom Label
Alternate Label
Style
Operation
Mounting
Candela
Horn Type
Tone
Table 7-8.TrueAlert ES AV-L Point Editing Options
Option
This field is used to describe the appliance's function, location, or other descriptive
information.
This field is used to enter an alternative description of the appliance.
Select the Style that corresponds to the appliance or device you are programming.
• Indoor.
• Weatherproof UL/
ULC
Available candela
options:
Select the type of operation the appliance will signal.
General Evac.
Other
Only a wall-mounted appliance is allowed.
Select the candela output of the appliance. The selection varies according to the
appliance style.
Broadband
BROADBAND
4007ES Panel Programmer Manual (579-1167)
Description
System Default. Selecting this option sets the candela value
to the one selected in the System Option tab.
15 candela
30 candela
75 candela
Hardware. Selecting this option sets the appliance to the
setting indicated on the appliance's configuration switch or
jumper.
The strobe is automatically associated with the "ALL VISUAL"
VNAC by default. The "alarm/alert" switch on the device must
be set to "Alarm".
When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular
VNAC and that the VNAC must be specified by the user.