Simplex 4007ES Programmer's Manual page 109

Fire alarm systems
Hide thumbs Also See for 4007ES:
Table of Contents

Advertisement

Custom Control, Continued
Suppression
Table 9-5 describes actions and their corresponding responses.
Release Use
Cases
Action
First detector is
triggered.
Abort switch is
pressed and held.
Second detector is
triggered while abort
switch is still pressed.
Keep the abort switch
pressed for more than
one minute.
Abort switch is
released
Use Case #4: Immediate Release
This use case is the simplest case. No abort switch, no release timers and no cross zone
verification.
Specific Configuration
IDNET points
True Alert Zone
AuxNAC
Create a Hazard Area in Custom Control, Suppression Release Wizard,
• Create Hazard Area window.
Table 9-5. IRI Abort, Actions and Releases
Response
RELSIG turns on low cadence (Temporal). RELWVIS turns on.
No change.
• RELSIG goes on high cadence (March120). RELWVIS stays on.
• SRP output does not turn on including after Automatic Release Timer expires.
After 10 seconds or the remaining value of the release timer, whichever is greater,
RELSIG goes on steady. RELWVIS stays on. RELVIS goes on. SUPRELS NAC
goes on steady and SRP output goes on steady.
Notes:
• If a second alarm condition occurs while the Abort switch is still pressed, the
automatic release timer resets to the value that has been configured for it. It
begins to count down and will stop at 10 seconds. When the abort switch is
released, the panel starts the release timer countdown at the value of the
countdown timer or at 10 seconds, whichever is greater.
• Pressing the abort switch again and releasing it, when a second alarm is
triggered, has no effect.
• Manual release point: MBZAM with SSDUMP point type at address M1-11-0.
• Automatic Release Points: One Smoke detector devices with SUPDET point types at
address at M1-18-0.
• SRP: One SRP (RELEASE) with point type SUPRELS at address M1-36-0.
• SIG913 is configured as RELSIG (Releasing horn circuit) and has at least one audible
device from the IDNAC channel.
• SIG915 is configured as RELVIS (Releasing Visual Signal) and has at least one visual
device from the IDNAC channel.
• SIG3 set as SUPRELS point type.
1. Hazard Area Name: Area 1
2. Comments: n/a
4007ES Panel Programmer Manual (579-1167)
9-25
Continued on next page