Step 2. Specifying Initial Data And Options - Simplex 4007ES Programmer's Manual

Fire alarm systems
Hide thumbs Also See for 4007ES:
Table of Contents

Advertisement

Custom Control, Continued
Step 2. Specifying
The next screen, shown in Figure 9-31, prompts you to specify the following information.
Initial Data and
Options
• Custom Control Program Number. This is the program number under which the
suppression release custom control equations created by the wizard are stored. In the case of
a 4007ES FACP, Program # 3 is the only one that can be used.
• Cross Zone (Dual Detector). Check this box to enable cross-zoned (dual detector)
operation. Cross-zoned applications require that two automatic initiating devices in different
areas enter an alarm state before the releasing appliance can activate.
Note: To achieve true cross zoning, the initiating devices must be wired to either Monitor cards or ZAMs.
• First Stage Audible Notification. Click on the drop down list box and set the audible
notification appliance pattern used for the first stage of a cross-zone (dual detector) alarm.
Choices include Slow March Time, Temporal, or Fast March time*. When cross-zoned
(dual detector) is enabled, this is the audible NAC tone pattern plays following activation of
the first detector. When the second detector activates, the pattern is always Fast March. This
option is not applicable if Cross Zone (Dual Detector) check box is not selected.
Click Next to continue programming when you have set these options to the appropriate
values.
Dual detector operation, which requires two detectors to activate, can use TrueAlarm initiating
devices.
* Note: Fast March time is not recommended, for example, there would be no change in pattern when
transitioning from the first stage alarm to the second stage alarm.
Figure 9-31. Cross Zone (Dual Detector) Options
4007ES Panel Programmer Manual (579-1167)
9-28