Releasing Specific Controls and Indications, Continued
Releasing Service
Signal Silence
Programming -
Optional
(Pushbutton and
Yellow LED)
4. Disable the Suppression Release Wizard to delete the default equation written by the
Suppression Release Wizard to silence the NACs on system silence. If it is not deleted it
will still silence the hazard area.
a.
b.
c.
d.
Right click the wizard for that hazard and select enable Manual Edit.
Click Yes in the confirmation box that follows.
Return to your custom control equations and find the equation that the Suppression Release
Wizard labeled On System Silence - yourhazardname
Right click and select Delete.
A-15
4007ES Panel Programmer Manual (579-1167)