Distributed Configuration - Simplex 4007ES Programmer's Manual

Fire alarm systems
Hide thumbs Also See for 4007ES:
Table of Contents

Advertisement

Adding or Editing Network Information, Continued
Programming
5. Click on the List tab at the top of the programmer. When the List window appears, click on
Distributed
the General List subtab at the bottom of the window. Scroll through the list, right click on
Network Reset
L105 and select Tag List.
6. Click on the Filter icon at the top of the Tag List. When the list of choices appears, click on
the Network Externals check box. All of the External Points appear.
7. Click on every entry for P212 and press the space bar to add the entry to L106.
8. Repeat Steps 3 through 7 for every node on the network.
Distributed
The digital pseudo points P463 and P464 are used to raise a trouble when a CO sensor is within
Configuration
6 or 12 month of its expiration date. A transition from off to on of the digital pseudo point will
trigger a check on all CO sensors within the local panel. On site, where multiple panels are
linked together over the network, it is possible to synchronize the 2 digital pseudo points on
every node. To do so, the remote node must declare the local node's P463 as External, since
P463 and P464 are always public by default. Once P463 is imported to the remote node's job,
its L170 is automatically updated to include the imported digital pseudo point. The same
applies to P464 and L171. So when the remote node P463 is turned on, default SMPL equation
0-164 will turn the local node's P463 to on. To declare an external point, refer to the section
"Procedure to Declare External Points" in this chapter.
1. Open the network job by using the network programmer.
2. Open the job for the node that will serve as the central reset node.
3. When the ES Panel programmer appears, click the Network tab at the top of the
programmer.
4. When the Network window appears, click the Network Points subtab at the bottom of the
Network window.
5. Right click in the Network window.
6. When the choices appear, click on Edit Externals. A dialog box appears.
7. Click on the drop-down list box and choose one of the nodes on the network.
8. Click on OK to close the dialog. A tag list containing the public points from the selected
node appears.
9. Click on P463 and press the space bar to select the point.
10. Click on P464 and press the spacebar to select the point.
11. Click OK to close the taglist.
12. Repeat Steps 5 to 11 for every node on the network.
Node 4
L170
1:P463
2:P463
3:P463
L171
1:P464
2:P464
3:P464
Figure 13-12. Distributed Configuration
13-11
4007ES Panel Programmer Manual (579-1167)
Node 1
L170
2:P463
3:P463
4:P463
L171
2:P464
3:P464
Node 2
4:P464
L170
1:P463
3:P463
Node 3
4:P463
L171
L170
1:P464
1:P463
3:P464
2:P463
4:P464
4:P463
L171
1:P464
2:P464
4:P464

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4007es hybrid

Table of Contents