Simplex 4007ES Programmer's Manual page 59

Fire alarm systems
Hide thumbs Also See for 4007ES:
Table of Contents

Advertisement

Point Editing for TrueAlert Device, Continued
TrueAlert ES VO
Use this device type to edit TrueAlert ES Visual Only (VO) appliances.
The following editing options are available for this appliance:
Appliances Point
Editing
Custom Label
Alternate Label
Style
Operation
Mounting
Candela
Note: The "Copy/Paste/ Special Paste" feature can be used to configure multiple devices identically.
Table 7-2. TrueAlert ES VO Point Editing Options
Option
This field can be used to describe the appliance's function, location, or other
descriptive information.
This field is used to enter an alternative description of the appliance.
Select the Style that corresponds to the appliance or device you are programming.
• Indoor.
Available candela
options:
• Weatherproof UL.
Available candela
options:
• Weatherproof ULC.
Available candela
options:
Select the type of operation the appliance will signal.
General Evac.
Other
Select the mounting location of the appliance: wall-mounted or ceiling-mounted.
Select the candela output of the appliance. The selection varies according to the
appliance style.
4007ES Panel Programmer Manual (579-1167)
Description
System Default. Sets the candela value to the one selected in
the System Option tab.
15 candela
30 candela
75 candela
110 candela
135 candela
185 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
System Default. Sets the candela value to the one selected in
the System Option tab.
15 candela
75 candela
WP 75 candela
WP 185 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
System Default. Sets the candela value to the one selected in
the System Option tab.
20 candela
30 candela
75 candela
Hardware. Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.
The strobe is automatically associated with the "ALL VISUAL"
VNAC by default. The "alarm/alert" switch on the device must
be set to "Alarm".
When this mode is selected the user is confirming that the
strobe does not have a default assignation to a particular VNAC
and that the VNAC must be specified by the user.