Editing Standard Component Properties, Continued
48-LED Module
In High Level Mode:
1. Select a column and then a point that needs to be edited. LED pairs are yellow and red.
2. Select the Mode from the Mode drop-down list. Under this mode, only three options are
available. If an error is detected, a red "X" is displayed in the HW Ref column. Pass the
mouse over the row to display the tool tip describing the problem.
3. Create Reference Address for the points by pressing F9.
4. Enter a point custom label. This label should make the point easily identifiable.
5. When editing the 8 points of the Display Column 6, LED pairs can be either yellow/red or
yellow/green.
6. Repeat for each point that needs to be edited.
In Low Level Mode:
1. Select a column and then a point that needs to be edited. Point type:
2. Select the Mode from the Mode drop-down list.
3. Create Reference Address for the points by pressing F9.
4. When editing the 8 points of the Display Column 6:
• OO : On/Off
• TO: Trouble On
• Select an address from the table. Scroll through the list and press the space key to
select an address. A ">>" symbol appears indicate that it is selected.
• For the even-numbered points 2 through 40, the default LED point type is LEDRED.
• For the odd-numbered points 1 through 39, the default LED point type is
LEDYELLOW.
• Select an address from the table. Scroll through the list and press the space key to
select an address. A ">>" symbol appears indicate that it is selected.
• For the even-numbered points, the default LED point type is LEDRED. The address of
the point depends on the LED point type selected. The point type can be changed to
LED green.
• For the odd-numbered points, the default LED point type is LEDYELLOW.
6-19
4007ES Panel Programmer Manual (579-1167)