Simplex 4007ES Programmer's Manual page 49

Fire alarm systems
Hide thumbs Also See for 4007ES:
Table of Contents

Advertisement

Editing Standard Component Properties, Continued
Editing the Serial
The 4007-9806 serial DACT interface card can be programmed per point or by event.
DACT Card Per
The 4007-9806 serial DACT per point has six main tabs to edit. The Card Properties tab, the
Point
Basics tab, the Event Codes tab, the Local Points tab, the Point Types tab, and the Points tab.
To edit the Card Properties tab per point:
1. The panel assigns an address when a DACT card is added. Set the card address to match the
programmer assigned address.
2. Enter the card's custom label. This label should make the card easily identifiable.
3. Select a card address, from 0 to 31.
The following fields in the tab are filled by the programmer and cannot be edited:
To edit the Basics tab (Figure 6-19):
The Basics tab can be used to set up the basic communication information of the DACT to
DACR link. The following fields in the tab can be edited:
To edit the Event Codes tab (Figure 6-20):
The Event Codes tab allows you to edit the
event codes associated with each of the
4007ES Panel point types.
1. Click on the Point Types drop-down list box
and select the point type whose event codes
needs to be changed. (The Next and
Previous buttons allow you to scroll
through the list without clicking on the
drop-down list box.)
2. Click on the Enable Edit checkbox at the
top left of the window.
3. A warning window appears. Click on Yes.
Note: Do not edit event codes without prior authorization and direction from the central station.
4. The non-editable fields remain grayed out. Define the appropriate event codes for both the
Event and the Restoral columns.
5. Click Apply > OK to confirm the edits.
• Card description
• Card default label
• Annunciator address
• Box number
• Bay number
• Location
• Phone and Account Numbers
- Primary (1)#
- Secondary (2)#
- Account (1)#
- Account (2)#
• Central Station Line #
• Dial Mode
- Tone
- Pulse
- Tone else Pulse
• Miscellaneous
- Report AC Failure Delay
- Test Report Time
- Send Unmapped Points
- IP Communicator
• Central Station Email Address. Check the box to enter an email address and the .CSV
file is automatically sent to Central Station. Automatic email can only be used with Per
Point DACTs and must be set up in advance with Central Station.
6-13
4007ES Panel Programmer Manual (579-1167)
Figure 6-19. DACT Card - Basics Tab
Figure 6-20. DACT - Event Codes Tab

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4007es hybrid

Table of Contents