Editing Standard Component Properties, Continued
Editing the Serial
To edit the Local Points tab (Figure 6-21):
DACT Card
The Local Points tab allows you to edit the local points associated with each of the 4007ES
Panel point types.
1. Click on the Enable Edit checkbox at the
top right of the window.
2. A warning window appears. Click on Yes.
Note: Do not edit local points without prior
3. The non-editable fields remain grayed out.
Define the appropriate local points for
both the Event and the Restoral columns.
4. Click Apply > OK to confirm the edits.
To edit the Point Types tab (Figure 6-22):
The Point types tab allows you to add new point types, delete, or edit existing point types.
To edit an existing point:
1. Click on a point in the grid.
2. Edit the appropriate fields for
both the Event and the
Restoral columns.
3. Edit the SDACT point type
name and the SDACT point
type description if necessary.
4. Click Apply to confirm the
edits
To delete an existing point:
1. Click on a point in the grid.
2. Click on Delete.
3. Click on Apply to confirm
the edits.
To add a point:
1. Click on Add.
2. Edit the SDACT point type name and the SDACT point type description. These labels
should make the points easily identifiable.
3. Edit the appropriate fields for both the Event and the Restoral columns.
4. Click Apply > OK to confirm the edits.
Note: Do not edit local points without prior authorization and direction from the central station.
authorization and direction from the central
station.
6-14
4007ES Panel Programmer Manual (579-1167)
Figure 6-21. DACT - Local Point Tab
Figure 6-22. DACT - Point Types Tab