Point Editing for TrueAlert Device, Continued
TrueAlert ES AV-L
Appliance Point
Editing
Coding Type
Volume
Note: The "Copy/Paste/Special Paste" feature can be used to configure multiple devices identically.
Table 7-8. TrueAlert ES AV-L Appliance Point Editing, Continued
Option
Select the Coding Type to set the cadence of the audible signal.
System Default
Temporal
March 20
March 60
March 120
On Steady
Temporal 4
Set the appliance volume:
High
Low
Hardware
4007ES Panel Programmer Manual (579-1167)
Description
This sets the coding to the value determined in the System
Option tab.
A three-pulse coding pattern consisting of three ½ second
pulses, each separated by a ½ second silence. Each three
pulse group is separated by 1 ½ seconds of silence. Pattern
repeats until alarm silence.
A coded signal that uses 20 beats per minute. Each beat
consists of 1 ½ second pulse on, 1 ½ second off. Pattern
repeats until alarm silence.
A coded signal that uses 60 beats per minute. Each beat
consists of ½ second pulse on, ½ second off. Pattern repeats
until alarm silence.
A coded signal that uses 120 beats per minute. Each beat
consists of ¼ second pulse on, ¼ second off. Pattern repeats
until alarm silence.
On steadily.
A CO gas warning that is a repeated sequence of four cycles
of 100 msec on with 100 msec off, followed by 5 seconds off.
To use this option the appliance's configuration control must
be set to Panel.
To use this option the appliance's configuration control must
be set to Panel.
Selecting this option sets the appliance to the setting
indicated on the appliance's configuration switch or jumper.