Programming Distributed Network Reset - Simplex 4007ES Programmer's Manual

Fire alarm systems
Hide thumbs Also See for 4007ES:
Table of Contents

Advertisement

Adding or Editing Network Information, Continued
Programming
11. Click on the Filter icon at the top of the Tag List. When the list of choices appears, click on
Central Network
Reset
12. Click on the entry for P211 and press the space bar.
13. Repeat Steps 10 through 12 for every node on the network.
Programming
With Distributed Network Reset, the following occurs:
Distributed
• Each node controls its own General Alarm Points.
Network Reset
• System Reset can be initiated from any node and all other nodes may also experience the
reset operation.
• System Points involved: P212 Detector/System Reset, and 105 External Entire System Reset
Points.
To configure Distributed Network Silence, do the following on each node.
1. Open the network job, using the network programmer.Open the job for one of the nodes.
2. When the ES Panel programmer appears, click on the Network tab at the top of the
programmer. When the Network window appears, click on the Network Points subtab at the
bottom of the Network window.
3. Right click in the Network window. When the choices appear, click on Edit Externals. A
dialog similar to the following appears. Click on the drop down list box and choose one of
the nodes on the network.
4. Click OK to close the dialog. When you do this, a tag list containing the public points from
the selected node appears. Click on P212 and press the space bar to select the point. Click
OK to close the taglist.
the Network Externals check box. All of the External Points appear.
Figure 13-10. Distributed Network Reset
Figure 13-11. Choose Node
4007ES Panel Programmer Manual (579-1167)
13-10
Continued on next page