Custom Control, Continued
Step 3. Specifying
• NYC Abort (Does not comply with UL 864). Pressing the Abort switch does the
Abort Switch
following:
Operation
Click Next to continue.
Step 4. Setting
Using the next screen you can set values for the Manual Release, Detector Release, and the
Releasing Cutout.
Timer Options
• Warning bell and strobe turn on (NAC associated with RELISIG point type).
• Evacuation visuals turn off (NAC associated with RELWVIS point type).
• Evacuation audibles turn off (NAC associated with RELSIG point type).
• Automatic Release Timer countdown stops at its current value.
Releasing the Abort switch starts the 90-second Investigate Timer. When the
Investigative Timer expires, the following occurs:
• Warning bell and strobe turns off
• Evacuation visuals turn on
• Evacuation audibles turn on at 120 BPM
• Reload the Automatic Release Timer with the programmed value
If the abort switch is pressed and released after the second alarm while the investigation
timer is running, the investigation timer does not reset and continues to countdown until
it reaches zero. When the investigation timer reaches zero, the evacuation visuals and
audibles turn back on and the automatic release timer begins to countdown. If the abort
switch is pressed and released again while the automatic release timer is running, a new
full cycle of investigation and automatic release delay starts.
Figure 9-33. Timer Configuration Options
9-30
4007ES Panel Programmer Manual (579-1167)
Continued on next page