Panel Information and Configuration, Continued
System Options
Fire
Reminder
Pri2
Reminder
Supv
Reminder
Trbl
Reminder
Local
Annunciation
Table 4-3. Active Status Reminder System Options
Option
The Fire Reminder option programs the system to periodically sound the
piezo if an uncleared Alarm condition exists at the panel, thereby reminding
system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled Enabled is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
The Pri2 Reminder option programs the system to periodically sound the
piezo if an uncleared Priority 2 Alarm (security) condition exists at the panel,
thereby reminding system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled Enabled is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
The Supv Reminder option programs the system to periodically sound the
piezo if an uncleared supervisory condition exists at the panel, thereby
reminding system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled Enabled is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
The Trbl Reminder option programs the system to periodically sound the piezo
if an uncleared Trouble condition exists at the panel, thereby reminding
system operators about the uncleared condition.
By default, this option is enabled and the Resound Time is set to 8:00.
To modify the Active Status Reminder settings, do the following:
1. Make sure the box labeled Enabled is checked.
2. Set the interval at which the piezo should sound. The range is from 0 to
18 hours. The default is 8 hours.
If there is a per point serial DACT in the system, this setting specifies whether
the piezo on the local panel will sound. This option is useful in situations
where the panel is located in a public area (such as a lobby) and the occupant
does not want the piezo repeatedly sounding.
4007ES Panel Programmer Manual (579-1167)
Description
4-5