Configuration - Simplex 4100-9600 Installation Instructions Manual

Communication and audio interface modules
Hide thumbs Also See for 4100-9600:
Table of Contents

Advertisement

Configuration

Overview
The TIC and all other modules to be mounted in the transponder cabinet and attached expansion
bays must be configured to operate correctly in the system via their DIP switch and jumper ports.
This section describes the hardware configuration for TICs and the Network Audio Riser
Controller Module.
Setting the Address
The TIC and Network Audio Riser Controller Module device addresses are set via DIP switch
SW1, which is a bank of eight switches. From left to right (see Figure 3,) these switches are
designated as SW1-1 through SW1-8. The function of these switches is as follows:
SW1-1. Set this switch to ON.
SW1-2 through SW1-8. These switches select the module's address. Refer to Table 7
for a complete list of the switch settings for all of the possible module addresses.
Note: You must set these switches to the value assigned to the module by the
Programmer.
FigureTag FD4-844-01
4100 Comm. Baud
Rate. Switch
(SW1-1)
Must Be Set to
ON
ON
OFF
firealarmresources.com
DIP Switches SW1-2 through SW1-8
set the Card or Module Address.
Figure 4 shows an Address of 3.
1
2
3
4
5
6
7
Figure 3. DIP Switch SW1
10
8
Continued on next page