Environment-resistive Terminals
Programming Example
6-3-5

Mounting in Control Panels

Mounting Direction
114
When the Load Shorted Flag turns ON, either hold the status of the bit in the
user program and program to turn OFF all the Unit's outputs, or use an
Explicit message to read the contact that is shorted and turn it OFF. The
Short-circuited Bit is allocated in the fifth bit in the Unit's status information
area.
7
6
5
4
Short-circuited Bit
In the following programming example, output bits 00 to 07 of CIO 3200 turn
OFF when bit 05 of CIO 3300 (Load Shorted Flag) turns ON once. Output bits
00 to 07 of CIO 3200 will not turn ON again until the cause of the short is
removed and the outputs are reset by turning ON work bit W00001.
Setting Status
DRT2-OD08C
Node address 00, I/O allocated to CIO 3200, status allocated to CIO 3300.
W00001
330005
W00000
A
W00000
B
W00000
H
W00000
Use screws to mount the Environment-resistive Terminal in the Control Panel.
Environment-resistive Terminals cannot be mounted on a DIN Track.
Drill the mounting holes in the control panel according to the dimensions
shown in the dimensions diagrams and secure the Terminal with M5 screws.
The appropriate tightening torque is 1.47 to 0.5 N·m.
The terminal can be mounted in any of the following six directions.
Vertical
3
2
1
0
W00000
320000
320001
320007
Section 6-3