Using Another Company's Master Unit
Object
Section
instance 4
Instance type
Production
trigger
Transport type Server
Transport
class
Attribute
Service
Note The produced connection path and its length and the consumed connection path and its length depend
on the type of Slave being used, as shown in the following table.
Information
COS Cyclic
1
Cyclic
2
ID
Contents
1
State
Yes
2
Instance type
Yes
3
Transport class
Yes
trigger
4
Produced con-
Yes
nection ID
5
Consumed con-
Yes
nection ID
6
Initial comm.
Yes
characteristics
7
Produced con-
Yes
nection size
8
Consumed con-
Yes
nection size
9
Expected
Yes
packet rate
12
Watchdog time-
Yes
out action
13
Produced con-
Yes
nection path
length
14
Produced con-
Yes
nection path
15
Consumed con-
Yes
nection path
length
16
Consumed con-
Yes
nection path
17
Production
Yes
inhibit time
DeviceNet service
05
Reset
None
0E
Get_Attribute_
None
Single
10
Set_Attribute_S
None
ingle
Maximum number of instances
Get (read)
Set (write)
No
No
No
No
No
No
No
No
Yes
No
No
No
No
No
No
Parameter option
Appendix B
Value
01 (hexadeci-
mal)
12
---
---
01 (hexadeci-
mal)
See note.
00 (hexadeci-
mal)
00
00
See note.
See note.
0004 (hexadec-
imal)
202B2401
0000 (hexadec-
imal)
243