Omron DRT2 Series Operation Manual page 166

Devicenet slaves
Hide thumbs Also See for DRT2 Series:
Table of Contents

Advertisement

Analog Input Terminals
Setting Using the
DeviceNet Configurator
1,2,3...
Moving Average
Processing
Conversion points
2 points
1 point
1. Double-click the icon of the Analog Slave to be set in the Main Window and
open the Edit Device Parameters Window. (From the Maintenance Mode
Window, click the right mouse button over the Slave icon and select Pa-
rameters and Edit.)
2. Click the General Tab and select the number of conversion points from the
pull-down menu under the Available Channel field. In the following exam-
ple, all four points are selected for conversion.
3. Click the Download Button, and then click the Reset Button to reset the
Unit.
4. Click the OK Button and exit the window.
Moving average processing calculates the average value (moving average) for
the previous eight inputs, and uses the resulting value as conversion data.
Details
Converting Inputs 0 and 1.
DRT2-AD
0
1
2
3
Used points
Converting Input 0 only.
DRT2-AD
0
1
2
3
Used points
Section 7-3
149