Omron DRT2 Series Operation Manual page 79

Devicenet slaves
Hide thumbs Also See for DRT2 Series:
Table of Contents

Advertisement

Remote I/O Terminal and Environment-resistive Terminal Functions
Manual Recovery Mode
Checking Using the
DeviceNet
Configurator
Setting to Automatic/
Manual Recovery Mode
1,2,3...
62
Note Refer to SECTION 6 Environment-resistive Slaves for the position of the
actual indicator.
When the cause of the short-circuit is removed and the corresponding contact
is correctly rewired, the short-circuit protection status is cleared by turning ON
the I/O power or the communications power. When the I/O power is OFF or
the output is OFF, the short-circuit protection status is maintained, so the
shorted locations can be easily identified from the indicator status during on-
site maintenance.
I/O Indicator Status when Short-circuit Detected
-A
-B
OFF
Lit red.
The box indicates the number of the corresponding connector.
Note Refer to SECTION 6 Environment-resistive Slaves for the position of the
actual indicator.
The method used to check information from the DeviceNet Configurator (Ver.
2.20 or later) is described here.
1. Turn ON the power to the DRT2-series Smart Slave.
2. From the Main Window, open the Network Configuration Window and dou-
ble-click or click the right mouse button over the icon of the DRT2-series
Smart Slave to be set. Select Parameter and Edit to display the Edit De-
vice Parameters Window.
From the Maintenance Mode Window, click the right mouse button over the
icon of the DRT2-series Smart Slave to be set. Select Parameter and Edit
to display the Edit Device Parameters Window.
3. Select the OUT Tab.
Select either Manual or Automatic for the external output load short-cir-
cuit recovery mode and click the OK Button.
4. Select the General Tab, click the Download Button, and then click the Re-
set Button to reset the Unit.
5. Click the OK Button.
Section 4-3