Omron DRT2 Series Operation Manual page 195

Devicenet slaves
Hide thumbs Also See for DRT2 Series:
Table of Contents

Advertisement

Analog Output Terminals
Setting Using the
DeviceNet Configurator
1,2,3...
178
Allocating User-defined I/O Data
Analog data that has been processed using math operations and Status Flags
can be selected and allocated as I/O in the Master in any combination. The
Configurator can be used to allocate the I/O in the Master.
This method is supported by CS/CJ-series DeviceNet Master Units only.
Note The settings in the Master are given priority, so the default connection path
settings in the Slaves are not required.
1. Double-click the icon of the Slave to be set in the Main Window and open
the Edit Device Parameters Window. (From the Maintenance Mode Win-
dow, click the right mouse button over the Slave icon and select Parame-
ters and Edit.)
2. Click the General Tab, select the Analog Slave to be set from the device
list, and click the Advanced Setup Button.
3. Click the Connection Tab, and select User Setup. Select Use Poll Con-
nection and then select Analog Data from the pull-down menu in the Con.
(Connection) Path field for output. At the same time, select Use Bit-Strobe
Section 7-4