Omron DRT2 Series Operation Manual page 203

Devicenet slaves
Hide thumbs Also See for DRT2 Series:
Table of Contents

Advertisement

Analog Output Terminals
Adjusting the Low Limit
Adjusting the High Limit
186
2. Select the Tab Page for the output to be adjusted, and click the Adjust-
ment Button. (At the same time set the output range again.)
3. Output the value that is equivalent to 0% from the Master Unit. Always per-
form adjustment with the 0% value.
4. Adjust the analog value that is output from the terminal using the Low Limit
slide bar, as shown in the following window. Repeat adjustments until the
correct 0% value is output from the output device. After compensation is
completed, click the Fix lower adjusting value Button.
5. To return to the default settings, click the Default Setting Button
6. Close the Adjustment Window, return to the General Tab, click the Down-
load Button, and then click the Reset Button to reset the Unit.
7. Click the OK Button and exit the window.
8. Output the value from the Master Unit that is equivalent to the Output Unit's
maximum (100%) value. Adjustment is best performed using the 100% val-
ue, but can be performed using a lower value.
9. Adjust the analog value that is output from the terminal using the High Limit
slide bar, as shown in the following window. Repeat adjustments until the
Section 7-4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents