Omron DRT2 Series Operation Manual page 150

Devicenet slaves
Hide thumbs Also See for DRT2 Series:
Table of Contents

Advertisement

Analog Input Terminals
Performance
Specifications
Item
Input points
Input signal range
Input range setting method
Maximum signal input
Input impedance
Resolution
Overall accuracy
25°C
–10 to 55°C
Analog conversion cycle
AD conversion data
Isolation method
I/O connection method
Standard accessories
Names and Functions
of Parts
Voltage input
4 points (Inputs 0 to 3)
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
• DIP switch: Inputs 0 and 1 share same setting, and Inputs 2 and 3 share same
setting.
• Configurator: Inputs 0 to 3 set separately.
±
15 V
1 M Ω min.
1/6,000 (full scale)
±
0.3% FS
±
0.6% FS
4 ms max./ 4 points
Note When the DeviceNet communications cycle is 4 ms and math operations
are not used.
–10 to 10 V range: F448 to 0BB8 hex full scale (–3,000 to 3,000)
Other ranges: 0000 to 1770 hex full scale (0 to 6,000)
AD conversion range:
Photocoupler isolation (between input and communications lines)
No isolation between input signal wires
Terminal-block connection
4 short bars for current input
DeviceNet
indicators
Communications
connector
Specifications
0 to 20 mA
4 to 20 mA
±
30 mA
Approximately 250 Ω
±
0.4% FS
±
0.8% FS
±
5% FS of the above data ranges.
Rotary switches.
Set the node address.
DIP switch
Sets the input
ranges.
Removeable terminal block
Section 7-3
Current input
133

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents