Omron DRT2 Series Operation Manual page 190

Devicenet slaves
Hide thumbs Also See for DRT2 Series:
Table of Contents

Advertisement

Analog Output Terminals
Output Range Settings
Setting Using the
DeviceNet Configurator
1,2,3...
2. Always set pin 8 to ON if the DIP switch is used to set the range. If this pin
is OFF, the DIP switch settings will not be enabled.
3. The DIP switch settings are read when the power is turned ON.
Output 0
Signal range
0 to 5 V
OFF
1 to 5 V
ON
0 to 10 V
OFF
–10 to 10 V
ON
4 to 20 mA
OFF
0 to 20 mA
ON
Output 1
Signal range
0 to 5 V
OFF
1 to 5 V
ON
0 to 10 V
OFF
–10 to 10 V
ON
4 to 20 mA
OFF
0 to 20 mA
ON
Use the following procedure to set the output range for each output using the
Configurator.
1. Double-click the icon of the Slave to be set in the Main Window and open
the Edit Device Parameters Window. (From the Maintenance Mode Win-
dow, click the right mouse button over the Slave icon and select Parame-
ters and Edit.)
2. Select the Tab Page for the output where the range is to be changed.
3. Click the Output Range field, and select the desired range.
4. Return to the General Tab, click the Download Button, and then click the
Reset Button to reset the Unit.
Pin 1
Pin 2
OFF
OFF
ON
ON
OFF
OFF
Pin 4
Pin 5
OFF
OFF
ON
ON
OFF
OFF
Section 7-4
Pin 3
OFF
OFF
OFF
OFF
ON
ON
Pin 6
OFF
OFF
OFF
OFF
ON
ON
173