Analog Output Terminals
Setting Output Value
for Errors
Setting Patterns
Low limit
High limit
Hold last state
Zero count
Output Ranges and Values
Output range
0 to 5 V
–0.25 V
1 to 5 V
0.8 V
0 to 10 V
–0.5 V
–10 to 10 V
–11 V
4 to 20 mA
3.2 mA
0 to 20 mA
0 mA
Setting Using the
DeviceNet Configurator
1,2,3...
4. To set the monitor value, click the Cumulated Count Tab, and input the de-
sired value in the Threshold Cumulated Counter field.
5. Return to the General Tab, click the Download Button, and then click the
Reset Button to reset the Unit.
6. Click the OK Button and exit the window.
The value that is output when communications errors (time-out and BusOff
errors) occur can be set for each output. The four output value settings are set
using the Configurator.
Outputs the values in the following table according to the output range.
Outputs the values in the following table according to the output range.
Holds and outputs the value from immediately before the error occurred.
Outputs the value when 0 is written from the Host. This setting will be affected by scaling
settings that are used.
Low limit
Note When a node address has been used more than once or a Unit error has
occurred, the current output will be 0 mA and the voltage output will be 0 V,
regardless of the setting.
1. Double-click the icon of the Analog Slave to be set in the Main Window and
open the Edit Device Parameters Window. (From the Maintenance Mode
Window, click the right mouse button over the Slave icon and select Pa-
rameters and Edit.)
High limit
5.25 V
5.2 V
10.5 V
11 V
20.8 mA
21 mA
Section 7-4
Hold last state
Holds value.
Holds value.
Holds value.
Holds value.
Holds value.
Holds value.
189